Anchor Bolt Types

Mechanical and Chemical Concrete Anchors

Anchor bolts are critical for securing structural components, equipment, and fixtures to concrete or masonry. The selection of the right anchor type depends on the base material (concrete vs. masonry), the applied load (tension, shear, or both), whether the load is static or dynamic, and the environmental conditions. Wedge anchors (also called expansion anchors) are one of the most common heavy-duty anchors. They consist of a threaded stud with a tapered mandrel at the bottom and a separate expansion clip. When the nut is tightened, the clip is forced up the taper and expands against the walls of a pre-drilled hole in the concrete, creating a mechanical interlock. Wedge anchors are used in solid concrete only (not block or brick) and are available in diameters from 1/4 to 1-1/4 inch with embedment depths from 1-1/8 to 5-1/2 inches. The minimum concrete thickness must be at least 1.5 times the embedment depth. Sleeve anchors are similar but have an expansion sleeve that runs the full length of the embedment, making them suitable for both concrete and masonry (brick and block). Drop-in anchors are internally threaded female anchors that are hammer-set into a pre-drilled hole with a setting tool that expands an internal plug; a threaded rod or bolt is then threaded into the anchor. They are used for flush-surface applications and overhead installations. Epoxy anchors use a two-part adhesive injected into a clean, drilled hole before inserting threaded rod or rebar. Epoxy achieves the highest load values of any anchor type, can be placed close to edges and in cracked concrete, and provides excellent resistance to vibration and dynamic loading. However, epoxy must cure at specific temperature ranges and requires a longer installation time. In threaded rod hold-down systems for seismic shear walls, epoxy-set rods have become the standard over wedge anchors due to their superior performance in cracked concrete.

Anchor TypeBase MaterialTypical Diameters (in)Load CapacityBest Application
Wedge AnchorSolid concrete only1/4 - 1-1/4High (tension + shear)Structural steel, columns, heavy equipment
Sleeve AnchorConcrete, brick, block1/4 - 3/4MediumRailing, conduit, medium-duty
Drop-In AnchorSolid concrete1/4 - 3/4HighFlush overhead, threaded rod insertion
Epoxy / ChemicalConcrete (solid, cracked)#4 - #11 rebar sizesVery HighSeismic hold-downs, critical connections
Toggle BoltHollow wall, drywall1/8 - 1/2Low-MediumLight fixtures, shelving on drywall
Tapcon ScrewConcrete, brick, block3/16, 1/4LowSmall fixtures, electrical boxes, furring
Lag ShieldConcrete, brick, block1/4 - 3/4MediumLag screw into masonry

Installation and Edge Distance Requirements

All concrete anchors require minimum edge distances and spacings to achieve their published load values. Per ACI 318 and manufacturers' data, wedge anchors typically require a minimum edge distance of 5 to 10 anchor diameters and spacing of 10 anchor diameters. Anchors placed closer to an edge have reduced capacity due to concrete breakout failure. The hole must be drilled with a carbide-tipped masonry bit in a hammer drill to the specified diameter and depth, and the hole must be cleaned of all dust and debris (blow out with compressed air, brush, blow again). Epoxy anchors add an additional requirement that the hole must be absolutely clean for proper bond. In overhead installations, special injection pistons ensure the epoxy fills the hole without air pockets. Torque wrenches are essential for setting mechanical anchors to the manufacturer's torque specification without over-tightening and stripping the concrete.