The International Residential Code requires smoke alarms in specific locations in all new dwelling units and in existing dwellings undergoing renovation. NFPA 72 (National Fire Alarm Code) provides installation standards. The key requirement is that smoke alarms be interconnected so that when one alarms, all alarms in the dwelling sound.
| Location | Requirement | Notes |
|---|---|---|
| Each sleeping room | 1 smoke alarm inside bedroom | Or immediately outside if approved locally |
| Outside sleeping areas | 1 in immediate vicinity of bedrooms | In hallway/common area serving bedrooms |
| Each story | 1 per floor level | Including basements (not crawl spaces or uninhabitable attics) |
| Dwelling unit with split levels | On each level | If floor levels differ by ≥ 24", install on upper level |
| Requirement | Specification |
|---|---|
| Power source | AC primary with battery backup (new construction) |
| Interconnection | All alarms must be interconnected (hardwired or wireless) |
| Mounting — ceiling | ≥ 4" from wall |
| Mounting — wall | 4" — 12" below ceiling |
| Near ceiling fans | ≥ 3' from fan blade tips |
| Near bathrooms | ≥ 3' from bathroom door (to avoid steam nuisance) |
| Near kitchen | ≥ 10' from cooking appliances (or use photoelectric) |
| Stairways | At top of stairway on the ceiling |
Carbon monoxide alarms are required outside each sleeping area in dwellings with fuel-burning appliances or attached garages (IRC R315). CO alarms must be listed per UL 2034. New construction requires hardwired CO alarms with battery backup. Combination smoke/CO alarms must be interconnected with the smoke alarm system.