Plumbing vents serve three essential functions: they admit air to balance pressure in the drain-waste system (preventing trap siphonage), they allow sewer gases to escape above the roof, and they provide an oxygen supply for aerobic bacteria in septic systems. Every fixture trap must be protected by a vent within critical distance.
| Vent Size | Max Drainage Fixture Units Served | Max Developed Length |
|---|---|---|
| 1-1/4" | 2 DFU | 30' |
| 1-1/2" | 8 DFU | 60' |
| 2" | 24 DFU | 120' |
| 2-1/2" | 48 DFU | 180' |
| 3" | 84 DFU | 212' |
| 4" | 256 DFU | 300' |
| Requirement | Specification |
|---|---|
| Extension through roof | ≥ 6" above roof (≥ 12" if roof used for any purpose) |
| Extension above flood level rim | ≥ 6" above highest fixture flood level rim (for wall/floor vents) |
| Distance from operable window | ≥ 10' horizontally or ≥ 3' above window |
| Distance from air intake | ≥ 10' from any building air intake |
| Distance from property line | ≥ 10' from lot line |
| Vent through roof minimum size | ≥ 3" where roof surface allows snow buildup |
| Trap Size | Max Distance (1-1/2" slope) | Max Distance (1/4" slope) |
|---|---|---|
| 1-1/4" | 5' | 2'6" |
| 1-1/2" | 6' | 3'6" |
| 2" | 8' | 5' |
| 3" | 12' | 6' |
| 4" | 16' | 10' |