GFCI Requirements — NEC Protection Zones

How GFCIs Work

A Ground-Fault Circuit Interrupter monitors the current flowing in the hot and neutral conductors. If there's an imbalance of 4—6 milliamps (indicating current leaking to ground through a person or object), the GFCI trips within 1/30th of a second. GFCIs are available as circuit-breaker types (in the panel), receptacle types, and portable types.

NEC-Mandated GFCI Locations

LocationNEC SectionDetails
Bathrooms210.8(A)(1)All 125V receptacles, all bathroom receptacles
Garages & accessory buildings210.8(A)(2)All 125V receptacles (with exceptions for dedicated appliances)
Outdoors210.8(A)(3)All 125V receptacles, must be WR type
Crawl spaces (at or below grade)210.8(A)(4)All 125V receptacles
Unfinished basements210.8(A)(5)All 125V receptacles (with exceptions)
Kitchen countertops210.8(A)(6)All 125V receptacles serving countertop surfaces
Within 6' of sink210.8(A)(7)Any sink — kitchen, laundry, bar, utility
Boat hoists210.8(C)All 125V—250V receptacles
Laundry areas210.8(A)(10)All 125V receptacles (since 2017 NEC)
Damp/wet bar sinks210.8(A)(9)All 125V receptacles serving wet bar areas

GFCI Requirements by NEC Edition

NEC EditionNew GFCI Requirements Added
2020/2023All 125V—250V receptacles in kitchens, GFCI for all basement receptacles
2017Laundry area receptacles, all kitchen branch circuits
2014Dishwashers (hardwired or cord-connected)
2011Garage receptacles (all, not just accessible)
2008All kitchen counter receptacles (previously only within 6' of sink)