The National Electrical Code (NEC) Article 210.52 specifies minimum receptacle outlet locations and spacing for habitable rooms, kitchens, bathrooms, and other areas. The primary rule is the "6-foot/12-foot rule": no point along a wall line should be more than 6 feet horizontally from a receptacle outlet, meaning receptacles are spaced no more than 12 feet apart along the wall.
| Location | Requirement | Notes |
|---|---|---|
| Any wall ≥ 2' wide | At least 1 receptacle | Counts toward 6' rule |
| Wall spacing | ≤ 12' apart (6' from any point) | Measured along wall line, including corners |
| Floor receptacles | Counts if within 18" of wall | Must be listed for floor use |
| Countertop (kitchen) | ≤ 24" spacing, no point > 24" from outlet | All countertops ≥ 12" wide |
| Peninsula/Island | At least 1 receptacle | If long dimension ≥ 24" and short ≥ 12" |
| Room | Minimum Receptacles | Circuit Requirements |
|---|---|---|
| Kitchen | 2+ 20A small appliance circuits | GFCI required, no other rooms on circuit |
| Bathroom | 1+ within 3' of basin edge | GFCI required, 20A circuit (bathroom only or whole-house) |
| Laundry | 1+ on 20A circuit | GFCI required (since 2017 NEC), dedicated |
| Hallway (≥ 10') | At least 1 | Standard spacing rules apply |
| Outdoors (front & back) | 1+ each exterior grade | GFCI required, WR (weather-resistant) |
| Garage | 1+ per bay | GFCI required |
AFCI (Arc-Fault Circuit Interrupter): Required in virtually all habitable rooms per NEC 2023: living rooms, bedrooms, dining rooms, kitchens, laundry, hallways, and similar areas on 120V 15A/20A circuits. GFCI (Ground-Fault Circuit Interrupter): Required in bathrooms, kitchens, garages, crawl spaces, unfinished basements, outdoors, laundry areas, and within 6' of any sink.