IRC Section R310 requires every sleeping room (bedroom) and every basement used as habitable space to have at least one operable emergency escape and rescue opening (egress window or door). The opening must open directly to a public way, yard, or court. It must be operable from the inside without tools, keys, or special knowledge.
| Requirement | Minimum | Notes |
|---|---|---|
| Net clear opening area | 5.7 sq ft | 5.0 sq ft for grade-floor openings (below grade = 5.7) |
| Net clear opening width | 20" | Horizontal dimension of clear opening |
| Net clear opening height | 24" | Vertical dimension of clear opening |
| Sill height above floor | ≤ 44" | Measured from finished floor to bottom of clear opening |
| Requirement | Specification |
|---|---|
| Window well width | 36" minimum |
| Window well projection | 36" minimum |
| Window well depth > 44" | Requires permanent ladder |
| Ladder projection | ≥ 3" from wall, ≥ 12" rungs |
| Ladder width | ≥ 12" |
| Ladder reach | ≤ 18" below top of well |
| Window well drain | Gravel base or drain to daylight/foundation drain |
| Window Type | Rough Opening | Clear Opening |
|---|---|---|
| Casement (hinged) | 30" × 48" | ~5.8 sq ft |
| Double hung | 36" × 48" | ~5.8 sq ft (1/2 of total opening) |
| Slider | 48" × 36" | ~5.9 sq ft (1/2 of total opening) |
| Hopper (basement) | 38" × 24" | ~5.1 sq ft (verify with manufacturer) |