HVAC
1. CFM from Room Size
Room L×W×H (ft)
ACH (Air Changes/Hr)
CFM:
-
| Room Volume:
-
2. CFM from Duct Size
Duct Diameter (in)
Velocity (FPM)
CFM:
-
| Area:
-
3. Duct Velocity
CFM
Duct Diameter (in)
Velocity:
-
4. Duct Static Pressure (Velocity Method)
Velocity (FPM)
Density Factor
Velocity Pressure:
-
5. Friction Rate (Duct)
Total Static (in w.g.)
TEL (ft)
Supply/Return %
Friction Rate:
-
6. Air Changes Per Hour (ACH)
CFM
Room Volume (ft³)
ACH:
-
7. Ventilation CFM (ASHRAE 62.1)
People Count
Floor Area (ft²)
Space Type
Office
Classroom
Retail
Ventilation:
-
8. Exhaust CFM (Bathroom)
Room Volume (ft³)
Desired ACH
Exhaust CFM:
-
| Minimum:
-
9. Make-Up Air
Total Exhaust CFM
Make-Up Air %
Make-Up CFM:
-
| Shortfall:
-
10. Kitchen Hood CFM
Hood Length (ft)
Hood Width (ft)
Duty
Light
Medium
Heavy
Hood CFM:
-
11. CFM per Ton
Total CFM
Tons Cooling
CFM/Ton:
-
| Status:
-
12. Sensible Heat CFM
Sensible Load (BTU/hr)
ΔT (°F)
CFM:
-
13. Total Heat CFM
Total Load (BTU/hr)
Δh (BTU/lb)
CFM:
-
14. Duct Area from CFM
CFM
Max Velocity (FPM)
Duct Area:
-
| Round Dia:
-
15. Air Density Correction
Altitude (ft)
Air Temp (°F)
Density:
-
| Correction Factor:
-
16. Mixed Air Temperature
Return Air CFM
Return Air °F
Outside Air CFM
Outside Air °F
Mixed Air:
-
17. Economizer Changeover Temp
Return Air °F
OA Temp Setpoint
Economizer Active:
-
| Enthalpy Check:
-
18. Infiltration CFM
Room Volume (ft³)
ACH Natural
Infiltration:
-
19. Cooling Coil Velocity
CFM
Coil Face Area (ft²)
Face Velocity:
-
| Status:
-
20. Filter Face Velocity
CFM
Filter Area (ft²)
Face Velocity:
-
| Recom. Velocity:
-
21. Heat Loss - Walls
Wall Area (ft²)
R-Value
Indoor °F
Outdoor °F
Heat Loss:
-
22. Heat Loss - Windows
Window Area (ft²)
U-Factor
Indoor °F
Outdoor °F
Heat Loss:
-
23. Heat Loss - Roof
Roof Area (ft²)
R-Value
Indoor °F
Outdoor °F
Roof Heat Loss:
-
24. Heat Loss - Floor
Floor Area (ft²)
R-Value
Indoor °F
Ground °F
Floor Heat Loss:
-
25. Infiltration Heat Loss
Infiltration CFM
Indoor °F
Outdoor °F
Infiltration Loss:
-
26. Total Heat Loss
Walls (BTU/hr)
Windows
Roof
Infiltration
Total Heat Loss:
-
27. Cooling Load - Sensible
CFM
Room °F
Supply °F
Sensible Load:
-
28. Cooling Load - Latent
CFM
Room Humidity Ratio
Supply Humidity Ratio
Latent Load:
-
29. Total Cooling Load
Sensible (BTU/hr)
Latent (BTU/hr)
Total Load:
-
| SHR:
-
| Tons:
-
30. Equipment Capacity from Load
Total Load (BTU/hr)
Oversize Factor %
Equipment Size:
-
| Tons:
-
31. Heat Gain - Solar (Windows)
Window Area (ft²)
SHGC
Solar Radiation (BTU/hr/ft²)
Solar Heat Gain:
-
32. Heat Gain - People
People Count
Activity Level
Seated
Light Work
Heavy Work
Sensible:
-
| Latent:
-
| Total:
-
33. Heat Gain - Lighting
Watts
Fixture Type
LED
Fluorescent
Incandescent
Heat Gain:
-
34. Heat Gain - Equipment
Equipment Watts
Diversity Factor
Heat Gain:
-
35. Duct Heat Gain/Loss
Duct Area (ft²)
R-Value
ΔT (°F)
Heat Gain/Loss:
-
36. U-Value from R-Value
R-Value
Surface Film (optional R)
U-Value:
-
37. CLTD Cooling Load
Area (ft²)
U-Factor
CLTD (°F)
Cooling Load:
-
38. Building Envelope UA
Wall U-Value
Wall Area
Roof U-Value
Roof Area
Total UA:
-
39. Degree Days - Heating
Avg Daily °F
Days
Base °F
HDD:
-
| Total:
-
40. Degree Days - Cooling
Avg Daily °F
Days
Base °F
CDD:
-
| Total:
-
41. Furnace AFUE Savings
Annual Therms
Old AFUE %
New AFUE %
Cost/Therm ($)
Annual Savings:
-
42. Heat Pump COP
Heat Output (BTU/hr)
Electrical Input (W)
COP:
-
| Efficiency Rating:
-
43. AC SEER Savings
Cooling Load (tons)
Old SEER
New SEER
Hours/Year
kWh Saved:
-
| Cost Saved ($0.12/kWh):
-
44. EER Calculation
Cooling Capacity (BTU/hr)
Power Input (W)
EER:
-
| SEER (approx):
-
45. Chiller Tonnage
Flow Rate (GPM)
ΔT (°F)
Tons:
-
| BTU/hr:
-
46. Boiler Efficiency
Input BTU/hr
Output BTU/hr
Efficiency:
-
| Stack Loss:
-
47. Cooling Tower Approach
Leaving Water °F
Wet Bulb °F
Approach:
-
| Range (10°F typical):
-
48. ERV Effectiveness
OA Temp °F
Supply After ERV °F
Return Air °F
Sensible Eff:
-
| Temp Rise:
-
49. HRV Sizing
Floor Area (ft²)
Bedrooms
Required CFM:
-
50. Dehumidifier Capacity
Room Volume (ft³)
Entering RH%
Desired RH%
Pints/Day:
-
51. Humidifier Capacity
Floor Area (ft²)
Desired RH%
Current RH%
Gallons/Day:
-
52. Furnace Sizing from Heat Loss
Heat Loss (BTU/hr)
Altitude (ft)
Furnace Size:
-
| Derate:
-
53. AC Sizing (Rule of Thumb)
Floor Area (ft²)
Climate
Moderate
Hot
Very Hot
Tons:
-
| BTU/hr:
-
54. Gas Pipe Sizing
Total BTU/hr
Length (ft)
Pressure
Low (7" w.c.)
Medium (2 psi)
Pipe Size:
-
55. Fuel Cost Comparison
Annual BTU Need
Electric Rate ($/kWh)
Gas Rate ($/therm)
Electric/Yr:
-
| Gas/Yr:
-
56. Heat Pump Balance Point
Design Heat Loss (BTU/hr)
Design Temp °F
HP Capacity @ 47°F (BTU/hr)
Balance Point:
-
57. Condenser Heat Rejection
Cooling Capacity (tons)
EER
Heat Rejection:
-
58. Chiller kW/Ton
Chiller kW
Tons
kW/Ton:
-
| Efficiency Rating:
-
59. Pump Brake HP
Flow (GPM)
Head (ft)
Efficiency %
BHP:
-
60. Fan Brake HP
CFM
Static Pressure (in w.g.)
Efficiency %
BHP:
-
61. Round Duct Size
CFM
Max Velocity (FPM)
Diameter:
-
62. Rectangular Duct from Round
Round Diameter (in)
Aspect Ratio
1:1
2:1
3:1
4:1
Rectangular:
-
63. Equivalent Round from Rectangular
Width (in)
Height (in)
Equivalent Round:
-
64. Equivalent Length of Fittings
Duct Diameter (in)
Fitting Type
90° Elbow
45° Elbow
Tee (thru)
Tee (branch)
Reducer
Equivalent Length:
-
65. Duct Insulation R-Value Required
ΔT Duct vs Ambient (°F)
Climate Zone
Cooling Dominant
Heating Dominant
Mixed
Min R-Value:
-
66. Duct Leakage Rate
System CFM
Leakage Class
Duct Surface Area (ft²)
Leakage CFM:
-
| % of System:
-
67. Register Throw Distance
CFM
Register Type
Ceiling Diffuser
Sidewall
Floor
Throw:
-
| Spread:
-
68. Diffuser Neck Size
CFM
Max NC (Noise)
Neck Diameter:
-
69. Grille Free Area
Grille Size (in)
Free Area %
Free Area:
-
| Max CFM:
-
70. Fire Damper Sizing
Duct Width (in)
Duct Height (in)
Fire Damper Size:
-
| Rating:
-
71. Plenum Box Sizing
CFM
Outlets
Plenum Size:
-
| Depth:
-
72. Duct Aspect Ratio Check
Width (in)
Height (in)
Aspect Ratio:
-
| Status:
-
73. Return Air Grille Sizing
CFM
Desired Velocity (FPM)
Grille Area:
-
| Size (approx):
-
74. Duct Weight Estimate
Duct Length (ft)
Perimeter (ft)
Gauge
26
24
22
20
Weight:
-
75. Duct Sealant Needed
Duct Length (ft)
Seams per Joint
Joints per 10ft
Sealant (gallons):
-
76. Duct Static Pressure (Friction Chart)
CFM
Duct Diameter (in)
Length (ft)
Pressure Drop:
-
| Velocity:
-
77. Duct Surface Area
Duct Width (in)
Height (in)
Length (ft)
Surface Area:
-
| Perimeter:
-
78. VAV Box Sizing
Design CFM
Min CFM %
VAV Box Size:
-
| Turndown:
-
79. Volume Damper Sizing
Duct Width (in)
Duct Height (in)
Damper Size:
-
| Opposed or Parallel:
-
80. Duct Liner Thickness
Required NC Reduction
Duct Type
Supply
Return
Liner:
-
81. Refrigerant Charge (Rule of Thumb)
System Tons
Line Set Length (ft)
Refrigerant Type
R-410A
R-22
R-32
Estimated Charge:
-
82. Superheat
Suction Line Temp (°F)
Suction Pressure (psig)
Refrigerant
R-410A
R-22
R-32
Superheat:
-
| Satur. Temp:
-
83. Subcooling
Liquid Line Temp (°F)
Head Pressure (psig)
Refrigerant
R-410A
R-22
R-32
Subcooling:
-
| Satur. Temp:
-
84. Target Superheat (TXV)
Return Wet Bulb (°F)
Outdoor DB (°F)
Target Superheat:
-
85. Psychrometrics - RH from DB/WB
Dry Bulb (°F)
Wet Bulb (°F)
RH:
-
| Depression:
-
86. Dew Point Temperature
Dry Bulb (°F)
Relative Humidity %
Dew Point:
-
| Condensation Risk:
-
87. Grains of Moisture
Dry Bulb (°F)
RH%
Altitude (ft)
Grains/lb:
-
| Humidity Ratio:
-
88. Steam Boiler Sizing
Heated Area (ft²)
Construction
Old (pre-1950)
Medium
New/Insulated
Boiler BTU/hr:
-
| Steam lbs/hr:
-
89. Hot Water Coil GPM
BTU/hr
Supply °F
Return °F
GPM:
-
| ΔT:
-
90. Hydronic Pipe Sizing
GPM
Max Velocity (fps)
Pipe Size:
-
| Actual Velocity:
-
91. Pipe Insulation Thickness
Pipe Temp (°F)
Ambient °F
Pipe Size
1/2" to 1"
1-1/4" to 2"
2-1/2" to 4"
Over 4"
Insulation:
-
92. Air Conditioner Refrigerant Line Size
System Tons
Line Set Length (ft)
Liquid Line:
-
| Suction Line:
-
93. Combustion Air Opening
Total BTU/hr Input
Location
Indoor
Confined Space
Opening Size:
-
94. Ventilation Effectiveness
Supply CFM
Breathing Zone CFM
Effectiveness (Ez):
| Required OA:
-
95. Sensible Heat Ratio
Sensible Load (BTU/hr)
Total Load (BTU/hr)
SHR:
-
| Coil Slope:
-
96. Chilled Water Coil GPM
Cooling Load (BTU/hr)
Chilled Water Supply °F
Chilled Water Return °F
GPM:
-
97. Natural Gas Consumption
Furnace BTU/hr
Runtime (hrs/day)
Days
Therms:
-
| Cost ($1.20/therm):
-
98. Cooling Tower Water Loss
Tower Tons
Cycles of Concentration
Evaporation:
-
| Blowdown:
-
| Make-up:
-
99. Air Handler Unit Weight
CFM
Coil Rows
Coil FPI
Est. Weight:
-
100. HVAC Unit Converter
Value
From
Tons
BTU/hr
kW
HP
CFM per Ton
To
BTU/hr
Tons
kW
HP
Result:
-